NRC finds Fort Calhoun did not have adequate flood safety procedures

Author: No Comments Share:

 

As a result of a Nuclear Regulatory Commission (NRC) inspection conducted from January 1 to June 21, 2010, the NRC determined that Fort Calhoun Station (FCS) did not have adequate procedures to protect the intake structure and auxiliary building against external flooding events.

Specifically, contrary to Technical Specification 5.8.1.a, the station failed to maintain procedures for combating a significant flood as recommended by Regulatory Guide 1.33, Appendix A, section 6.w, “Acts of Nature.” The NRC identified the following violation of NRC requirements associated with a yellow significance determination process finding in the mitigating systems cornerstone in inspection report 05000285/2010008 dated October 6, 2010:

Technical Specification 5.8.1.a, “Procedures,” states, “Written procedures and administrative policies shall be established, implemented, and maintained covering the following activities:

(a) The applicable procedures recommended in Regulatory Guide 1.33, Revision 2, Appendix A, 1978.” NRC Regulatory Guide 1.33, “Quality Assurance Program Requirements (Operation),” Appendix A, “Typical Procedures for Pressurized Water Reactors and Boiling Water Reactors,” Section 6, recommends procedures for combating emergencies and other significant events. Section 6.w, “Acts of Nature,” includes, in part, procedures for combating floods.

Contrary to Technical Specification 5.8.1.a, since 1978, written procedures and administrative policies were not maintained covering the applicable procedures recommended by NRC Regulatory Guide 1.33, Revision 2, Appendix A. Specifically, the licensee failed to maintain written procedures for combating a significant external flood as recommended by NRC Regulatory Guide, Appendix A, Section 6.w, “Acts of Nature.” The licensee’s written procedures did not adequately prescribe steps to mitigate external flood conditions in the Auxiliary Building and Intake Structure up to 1014 feet mean sea level, as documented in the Updated Final Safety Analysis Report [USAR].

The NRC reported that the station’s flood protection strategy was not fully effective during worst-case Missouri River flooding scenarios. The strategy required workers to install floodgates in front of the doors to the plant’s auxiliary building and intake structure, and then stack and drape sandbags over the top of the floodgates up to a height of five feet. The procedural guidance was inadequate because the cross-section on top of the floodgates would not support a stacked sandbag configuration that would retain five feet of moving water.


EVENT DESCRIPTION

During identification and evaluation of flood barriers (condition report (CR) 2010-2387), in response to NRC findings previously noted, unsealed through wall penetrations in the intake structure were identified that are below the licensing basis flood elevation. These penetrations were installed during the installation of upgrades to the plant fire protection system. As a result of the penetrations not being sealed, the intake structure was vulnerable to water inflow during an extreme flooding event. This inflow had the potential to affect the operability of both trains of safety related raw water pumps (ultimate heat sink).

On February 4, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 1717 CST (Event Number (EN) 46594). The report should have been made on September 9, 2009. (Documented in Condition Report (CR) 2011-0801) During the extent of cause analysis for this issue the following penetrations were identified as not having been reported.

 Unsealed penetrations were created during the installation of the original plant security system and were abandoned when the security system was replaced (approximately 1985). The penetrations for the “new” security system were appropriately sealed. The old penetrations were abandoned and not sealed. As a result of the penetrations not being sealed, the intake structure was vulnerable to water inflow during an extreme flooding event. This inflow had the potential to affect the operability of both trains of safety related raw water pumps (ultimate heat sink). On February 27, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 1640 CST (EN 46590). The report should have been made on January 27, 2011. (Documented in CR 2011-0609)

 Two additional conduits have been identified that are not sealed. These conduits penetrate the south wall of the auxiliary building near the transformers into Room 19 and were created as part of a station modification that was in progress at the time. Flooding through the penetrations could have impacted the ability of the station’s auxiliary feedwater (AFW) pumps to perform their design accident mitigation functions. On March 31, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 2232 CDT (EN 46716) (Documented in CR 2011-2470)

 A weakness in the flood protection strategy was discovered that would prevent protection of the raw water pumps for floods above 1007 feet-6 inches mean sea level (MSL). The flood protection strategy includes control of the intake cell level by throttling the sluice gates and running raw water pumps to maintain cell level. During the preparation of a calculation to demonstrate the validity of this method it was determined that the grid backwash pipe for each grid and the surface sluice penetrate the east wall of the intake structure through an unsealed penetration (7 penetrations). The grid backwash line is an 18 inch pipe passing through a 24 inch sleeve. Cell in-leakage through these penetrations would be beyond the capacity of the raw water pumps resulting in flooding of the intake structure and loss of the raw water pump function. On March 22, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 1611 CDT (EN 46690). (Documented in CR 2011-2161)

 An unsealed conduit (location 56E-S-43 in pull box 127) was identified that penetrates the auxiliary building into Room 56. Room 56 contains the safety related electrical switchgear. In addition, a drain flow path from the Chemistry and Radiation Protection (CARP) building into Room 23 which can drain into the rooms holding the Emergency Core Cooling System (ECCS) Pumps was identified. On April 8, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 1240 CDT (EN 46741). (Documented in CRs 2011-2072 and 2011-2448)

 A potential flooding issue in the Intake Structure, 1007’ 6” level was identified. The areas of concern are the holes in the floor at the 1007’ 6” level, where the screen wash header penetrates the ceiling of the Raw Water (RW) vault. There are five penetrations of concern. Flooding through the penetrations could impact the ability of the station’s RW pumps to perform their design accident mitigation functions. On May 26, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(D) to the NRC Headquarters Operation Office (HOO) at 0508 CDT (EN 46893). (Documented in CR 2011-5012)

 Three fittings into room 19 (auxiliary feedwater and plant air compressors) and fittings into room 56E (electrical switchgear) were found to contain no filling material. One additional fitting into room 56E that was thought to be capped was found to be open with a sheet metal box covering the inside access thereby obscuring inspections. The stations auxiliary feedwater and safety related electrical switch gear could be affected. On October 20, 2011, an eight (8) hour report was made under 10 CFR 50.72 (b)(3)(v)(B) and (D) to the NRC Headquarters Operation Office (HOO) at 1246 CDT (EN 47359). (Documented in CR 2011-8547) Since each of these incidents are events that are related (i.e., they have the same cause and consequences) and they were discovered during a single activity (i.e., investigation to correct the initial problem) then per NUREG 1022, Revision 2, these are being reported in one LER. This report is being made per 10 CFR 50.73(a)(2)(v)(B) and (D).

CONCLUSION

A root cause determination was prepared in connection with CR 2010-2387 which documents the causes of the problem. The following four (4) root causes explain why written procedures were inadequate to mitigate the external flood conditions prescribed by the Updated Safety Analysis Report (USAR). These root causes address the NRC issued yellow finding as well as the specific penetrations being addressed in this LER.

 Historically, when procedures for flooding protection were restructured or substantially augmented, a weak procedure revision process did not assure FCS met its USAR requirements.

 Supervisory and management oversight of work activities associated with external flood matters was not sufficient to prevent this issue from occurring.

 The FCS organization has not been effective in ensuring that performance deficiencies related to external flooding are adequately identified, evaluated, and resolved.

 Mindsets existed that FCS was “safe as is” relative to external flooding events. These mindsets collectively led to the incorrect conclusion that regulatory requirements were being met.

CORRECTIVE ACTIONS

Configuration changes were developed as needed and the penetrations sealed. Comprehensive corrective actions to address the root and contributing causes have been developed and will be addressed through the corrective action program.

SAFETY SIGNIFICANCE

The Fort Calhoun Station is required to be protected from flooding within the station’s licensing basis. The safety related equipment required to mitigate the consequences of an accident were affected by these findings. The openings could have jeopardized the ability of the safety related equipment to perform their design basis function during an accident. Other methods of removing decay heat and mitigating the consequences of a flooding event were available. Therefore, this external flooding concern has substantial importance to safety as indicated by the Yellow Finding issued for this event.

SAFETY SYSTEM FUNCTIONAL FAILURE

This event does result in a safety system functional failure in accordance with NEI-99-02.

PREVIOUS EVENTS

No licensee event report prior to this has identified the flooding issue. LER 2011-001 which had been written to report a flooding penetration has been cancelled as indicated in Reference 3 to the cover letter to this LER. The penetration is discussed in this LER.